Electricity bill guide
Power factor penalty: paying for power you never used.
Low power factor does not run a single extra machine, yet it can raise your bill in more than one place at once. Here is where it shows up, what causes it, and how plants keep it close to unity.
What power factor means
Motors, transformers and welding sets need two kinds of power. Active power (kW) does the useful work. Reactive power (kVAr) builds the magnetic fields those machines need to run, then flows back and forth without doing any work. Together they make up apparent power (kVA) — what your cables, transformer and the grid actually carry.
Power factor (PF) is the ratio of the two: kW ÷ kVA. At 1.00, every kVA does useful work. At 0.85, the supply carries about 18% more current than the work needs.
Four ways low power factor reaches your bill
Which of these applies depends on your state and tariff category — many plants face more than one.
- A PF surcharge. On kWh-billed tariffs, a surcharge usually applies when average PF falls below a threshold, commonly somewhere between 0.90 and 0.95. Some tariffs also give an incentive above it.
- More billed units. On a kVAh tariff, the units billed are kWh ÷ PF, so every point of PF lost becomes extra units on every hour of the month — no separate penalty line needed.
- A higher demand charge. Where demand is billed in kVA, low PF raises Maximum Demand and eats into your Contract Demand headroom.
- A reactive energy charge. Some tariffs bill reactive energy (kVArh) as its own line, so the cost shows up as a separate charge.
What it costs on a kVAh or kVA tariff
The same 400 kW of useful load, at different power factors:
| Power factor | kVA for 400 kW | Extra kVAh units |
|---|---|---|
| 1.00 | 400 | — |
| 0.98 | 408 | +2.0% |
| 0.95 | 421 | +5.3% |
| 0.90 | 444 | +11.1% |
| 0.85 | 471 | +17.6% |
| 0.80 | 500 | +25.0% |
kVA = kW ÷ PF. Extra units compare billed kVAh with PF 1.00 for the same kWh. Surcharge thresholds and rates differ by state, DISCOM and consumer category. Work out your own bill with the PF penalty calculator.
Moving from 0.90 to 0.98 cuts billed kVAh by about 8% for exactly the same production. On a plant using 1,00,000 units a month, that is roughly 9,000 fewer billed units every month.
What drags power factor down
- Lightly loaded motors and transformers. They draw almost the same reactive power at light load as at full load, while active power falls.
- Ageing or failed capacitors. Capacitors lose kVAr over the years, and a blown fuse or failed contactor can take a whole step out without anyone noticing.
- APFC panel faults. A controller stuck in manual, a wrong CT connection or a wrong target setting leaves correction doing less than it appears to.
- New loads, old correction. Capacitor banks sized years ago rarely match a plant that has since added machines.
- Harmonics. Drives, rectifiers and UPS systems distort current. That lowers true power factor and can overload capacitors that were never designed for it.
Overcorrection: the leading side
Correction sized for full load can push power factor leading when the plant runs light — at night, on holidays, between shifts. Many kVAh tariffs count leading reactive energy too, so overcorrection can cost money just like undercorrection. The aim is not maximum capacitance; it is PF close to 1.00 at every load.
How plants fix it
- Measure PF per panel, not only at the incomer. One average hides which feeder is pulling it down.
- Check capacitor health. Measure the current in each step against its rating; replace weak units before they fail outright.
- Correct close to the load. Fixed capacitors at large, steadily running motors take the load off the main bank.
- Keep the APFC in auto, with small enough steps to follow light-load hours.
- Use detuned or filter banks where drives and other non-linear loads are significant.
- Review after every major load change.
How KONDUKTOR® EMS helps
KONDUKTOR® EMS reads the multifunction meters already on your panels and shows live power factor for every meter against a 0.95 target, with lead or lag marked.
- Low-PF alerts tell your team the moment a panel slips, instead of at the end of the month.
- The power factor optimiser estimates the capacitor kVAr needed to reach your target and the rupee saving it would bring.
- History by shift and by panel shows when PF drops, and where — so the fix goes to the right feeder.
Common questions
What is a good power factor for a factory?+
Most plants aim for 0.95 or better, measured at the incomer. On a kVAh tariff the target is as close to 1.00 as possible at every hour of the day, without swinging into leading power factor.
Will adding more capacitors always help?+
No. Capacitors sized for full load can overcorrect when the plant runs light, pushing power factor leading. Many kVAh tariffs bill that as well. Correction should follow the load, which is what a healthy APFC panel does.
Why does our power factor drop at night or on weekends?+
Lightly loaded motors and transformers draw almost the same reactive power as at full load, while the active power falls. If fixed capacitors are switched off with production, or the APFC cannot step down finely enough, power factor moves away from unity in those hours.